Fire alarm page displays fire detector, manual call point, etc alarm information
List
Characteristics | ||
Stipulation | ||
Technical Data | ||
Structure and installation | ||
4.1 outside drawing | ||
4.2 inside construction drawing | ||
4.3 installation dimension drawing | ||
4.4 external wiring requirement | ||
4.5 external terminal layout drawing | ||
From installation to operation | ||
Basic functions | ||
6.1 start up | ||
6.2 register external device | ||
6.3 fire alarm | ||
6.4 monitoring information | ||
6.5 associate operation information | ||
6.6 fault alarm | ||
6.6.1 main power supply fault | ||
6.6.2 back-up power supply fault | ||
Menu operation function | ||
7.1 device information | ||
7.2 register information | ||
7.3 event record | ||
7.4 adjust time | ||
7.5associated setup | ||
7.5.1“or”1 logic setup | ||
7.5.2“or”2 logic setup | ||
7.5.3“and” logic setup | ||
7.5.4 pulse mode module | ||
7.6 system setup | ||
7.7 exit | ||
System self-check | ||
Lock key/Unlock | ||
Automatic/Manual switch | ||
Associated control | ||
Repair and Maintenance | ||
Notice | ||
Our service |
Hello
Welcome to Brightsky WorldConnecting newest technology 5iserise fire alarm system that will
Exceed your imaginationdirectly and plenty figure interface you will be the first time to feel our products’ reliabilityThe speed of fire alarm system is quicker than before, Brightsky Electronic
Co., Ltd quests system reliability and accurately that will be embodied completely.
This customer manual will let you know the super function of this kind of machine step by step.
Characteristics
² Graphic menu operation, new design
² Black box record function
² Detector condition display
² 250 intelligent bus device points capacity
² Alarm address information second-conversion accurate locating fire addresscan input in the form of pre-programming at desk computer or laptop
² All fire protection linkage operation relationship on-site programming
² Standard 485 interface, LAN network and remote communication function
Our Stipulations
In below descriptions
² all display letter or icon is buttonFor example
this is Down button
this is Reset button.
² Bus equipments which are including heat detectors, smoke detectors, manual call points, signal input module etc fire alarm touching equipments and Long-range control module etc Linkage control equipments.
² According to habit or description’s requirementsIt will be possible to use“Detector”letter can take place smoke detector, heat detector, manual call point, signal input module etc fire alarm touching equipments
² In the system, from No.001 to No.250, it is standard device address (detector, remote control module, etc), from No.251 to No.256, it is six multi-line control modules.
Technical Data
Main Power | AC 220V (+10%~-15%) 50HZ |
Back-up power supply | DC 24V2.3AHbuilt in |
Work consumption | Monitor state2.4WAlarm state10W |
Basic monitoring capacity | 5i series addressable device 250 pieces |
Direct external control contact | 6 pairs |
Polling cycle | 10 secondwhen Condition abnormity, single point continues to poll |
Signal transportation distance | 1500 meters. |
Wiring method | 1 5i series detectors——2-wire bus, non-polarity 2 5i series modules——2-wire bus, polarityT+——anodeT-——cathode |
Wire application | RVS-2×1.5mm2 two color plastic soft wire. |
Outside control touch points | KA1KA2 first time alarm, then closed immediately. YA1YA2 first time alarm under nobody controlled machine delay 2 minutes closed. |
Outside control touch points capacity | DC 30V2A. |
Operation Environment Temperature | 0~55 |
Relatively humidity | 95% |
External dimension | 440×340×82H×W×Tmm3 |
Installation form | Wall mounted type |
Weight | About12Kg |
Black box record data | Be able to save 500 recordsincluding open, close, alarm, fault and linkage information |
Linkage programming amount | 150 itemsor one, or two, with logic 50 items |
Room number conversion capacity | 250 pieces |
Room number conversion maximum allowable characters numbers | 30 pieces English characters |
Structure and installation
This control use wall mounted structureThere are 2.3Ah all sealed battery. Structure compact, Placement reasonably, Outline beautiful.
This is outline structure figure
This is the picture after you open the control panel front face
![]() |
Fire alarm controller should be installed in a room or place where can be controlled by manat the same time please install fire alarm controller on the wall. Normally fire alarm controller’s bottom is far away from the ground 1.5 metersIt will leave more than 0.5 meter distance in two sides. So that it will be easy operate and maintenance.
This is installation dimension drawing
Outside wiring requirements:
Signal wire is used RVS-2×1.5mm2 two colors plastic soft wirePower wire is used cross-sectional no less than 2.5mm2 inhibit wire.
External wiring terminal layout drawing
Directly output point button is one by one hardware buttonThough the controllers are “dead”, It can also start outside devices.
From installation to operation
1 Please be carefully to read this manual.
2 According “installation”chapterinstall this controller.
3 Using K ohm metes alarm bus is connecting ground resist must be more than 20K ohmAccording to fire extinguishing norm requirements to install detectors, MeanwhileAccording to position array figures, in order to check whether wiring is right or notEach of hardware whether is solid or not.
4 Start up.
5 According to fire code and project linkage operation relationship requirement, edit linkage operation relationship list based on “linkage operation programming”section.
6 Re open the panel, according to “register external device” section, register external devices.
Basic functions
Start
First time start please press control panel buttonMeanwhile please press main/ reserved power switchAfter controller initialized, indicator and sounder check itselfThen all devices of bus are loadingat the moment let loose
It takes about 2 minutes. Then system comes to normally monitor and control statePower of indicate in controller flashes. AttentionEach time restart system linkage is manually stateat the moment automatic/manually indicator always flashes.
Register outside devices
Register outside devices include to register detectors, modules etc connect with bus devices in the return circuit. Register operating, after start the controllerPress controller power switchwhen controller panel indicator flashes. Press registerafter finish to register, then indicate to have registered bus devices number and address code. Press
or
You can check the details’ listingPress
return to monitor and control state.
Fire alarm
Under normally monitor and control state, the controller patrols registered each of detectorsmonitor each of detectors current smoke consistency or temperature valuethen using the data to calculate and recognize by formula. Using the data according to formula calculate and recognize. If it is be fit for fire alarm conditionit can be put into fire alarm state. At the momentthe controller sounds the alarmthe controller panel’s fire alarm indicator flashesthe displayer indicates alarm address, number etc informationprinterwhen you install this printercan print alarm address, alarm timeMeanwhile the outside controller position KA1KA2 closedYA1YA2 begin to delayIf nobody controls controllerreduce sounder or reducethis position closed. If linkage position is in the automatic statethe controller is according to be the first time addressable linkage logic relation which can set out command in order to start corresponding long-range control moduleso that start or close outside devices.For example fire pumpSystem uses different pages approach among fire alarm, linkage and default information If there are two or many kinds of alarm information exist at the same timePlease press or
switch to another fire alarm type page, Press
or
you can check the up or down information.
Therein
fire alarm page displays fire detector, manual call point, etc alarm information